Compatible case size |
Other |
Outline drawing |
55Wx28Hx133D |
Weight |
0.16 kg typ |
Input Voltage |
AC |
85-264V |
Efficiency |
AC |
80% typ(100VAC)/82% typ(200VAC) |
Power factor |
|
Input changeover system |
Worldwide |
Safety |
IEC/EN60601-1 Ed3.1(CB/CE Marking), ANSI AAMI ES60601-1 Ed3.1(UL), CSA60601-1 Ed3.1(cUL), IEC/EN62368-1 2nd(CB/CE Marking), UL/CSA62368-1 2nd(UL/cUL),GB4943.1(CCC), PSE (ordinance clause 2) compliant |
High frequency current regulation |
|
EMI standard (Input feedback noise) |
VCCI/FCC/CISPR 32/EN55032 class B compliant |
CE marking |
Low Voltage Directive, EMC Directive,RoHS2.0 |
EMS immunity |
Electrostatic discharge: IEC61000-4-2 compliant Radiate, radio frequency electromagnetic fields: IEC61000-4-3 compliant Fast transient burst: IEC61000-4-4 compliant Lightning surge: IEC61000-4-5 compliant Conductive radio frequency electromagnetic fields: IEC61000-4-6 compliant Power source frequency magnetic immunity: IEC61000-4-8 compliant Voltage dips and fluctuation: IEC61000-4-11 compliant |
MTBF |
400,000h |
Operating temperature |
-10 to 70 deg.C |
Leakage current |
0.2mA max. (100VAC), 0.5mA max. (264VAC) |
Cooling systems |
Air-cooling without blower |
Insulation |
4kV AC/1minute between input and output (2MOPP),2kV AC/1minnute between input and FG,0.5kV AC/1minute between each output and FG |
Output ground connection |
Capacitor grounding |
Warranty |
Three years after delivery: If any defects belong to us, the defective unit shall be repaired or replaced at our cost. |